Lightwave Communications Server 3200 User Manual Page 81

  • Download
  • Add to my manuals
  • Print
  • Page
    / 88
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 80
77
The DC power source must be:
electrically isolated from any AC source
reliably connected to earth
capable of providing up to 100 Watts of continuous power
D.2 Overcurrent Protection
Overcurrent protection requirements:
10 Amp trip
double pole
fast trip
DC rated
Overcurrent protection devices (e.g., circuit breakers) must be provided as part of
each equipment rack, and are not included with the ConsoleServer.
The device must be located between the DC power source and the
ConsoleServer.
D.3 DC Supply Connector
The supply input connectors are provided with each ConsoleServer. However, the
conductors are not. See below for conductor specifications.
Conductor material: copper only
Wire gauge: 16 AWG
Insulation rating: 75°C minimum, low smoke fume, flame
retardant
Branch circuit cable insulation color: per applicable national electrical codes
Grounding cable insulation color: green/yellow
The cable type should be one of the following:
UL style 1028 or other UL 1581 (VW-1) compliant equivalent
IEEE 383 compliant
IEEE 1202-1991 compliant
Page view 80
1 2 ... 76 77 78 79 80 81 82 83 84 85 86 87 88

Comments to this Manuals

No comments